Technical data (short form)
Input voltage range 3x 400 V AC … 500 V AC
-20 % … +10 %
2x 400 V AC … 500 V AC
-10 % … +10 %
Mains buffering ≥ 25 ms (3X 400 V AC)
≥ 25 ms (3X 480 V AC)
Nominal output voltage (UN) 24 V DC
Setting range of the output voltage
(USet) 24 V DC … 29.5 V DC
Nominal output current (IN) 5 A
Static Boost (IStat.Boost) 6.25 A
Dynamic Boost (IDyn.Boost) 10 A (5 s)
Selective Fuse Breaking (ISFB) 30 A (15 ms)
Output power (PN) 120 W
Output power (PStat. Boost) 150 W
Output power (PDyn. Boost) 240 W
Efficiency typ. 89 % (400 V AC)
typ. 87.5 % (480 V AC)
Residual ripple < 30 mVPP
MTBF (IEC 61709, SN 29500) > 914000 h (40 °C)
Ambient temperature (operation) -25 °C … 70 °C
-40°C (startup type tested)
> 60 °C Derating: 2.5 %/K
Dimensions W/H/D 36 mm / 130 mm / 125 mm
Weight 0.6 kg