General specifications | ||
---|---|---|
Signal type | Analog output | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 2 | |
Systematic capability (SC) | SC 3 | |
Supply | ||
Connection | Power Rail or terminals 14+, 15- | |
Rated voltage | 19 … 30 V DC | |
Ripple | ≤ 10 % | |
Rated current | ≤ 45 mA at 24 V | |
Power dissipation | ≤ 1 W at 20 mA and 500 Ω load | |
Power consumption | ≤ 1 W | |
Input | ||
Connection side | control side | |
Connection | terminals 7-, 8+, (9+); 10-, 11+, (12+) | |
Input signal | 4 … 20 mA , limited to approx. 30 mA | |
Input voltage | open loop voltage of the control system ≤ 30 V | |
Voltage drop | approx. 6 V at 20 mA | |
Input resistance | field wiring open circuit : > 100 kΩ field wiring < 50 Ω : > 100 kΩ when using terminals 1, 2 and 4, 5 |
|
Output | ||
Connection side | field side | |
Connection | terminals 1+, 2-; 4+, 5- terminals 3+, 2-; 6+, 5- (no short circuit detection) |
|
Voltage | ≥ 13 V at 20 mA | |
Current | 4 … 20 mA | |
Load | 100 … 650 Ω , for terminals 1, 2; 4, 5 0 … 550 Ω , for Terminals 2, 3; 5, 6 |
|
Ripple | 20 mV rms | |
Line fault detection | breakage, load > 100 kΩ, short-circuit, load < 50 Ω | |
Fault indication output | ||
Output type | open collector transistor (internal fault bus) | |
Transfer characteristics | ||
Deviation | at 20 °C (68 °F), 4 … 20 mA < 0.1 % of full scale, incl. non-linearity and hysteresis |
|
Influence of ambient temperature | < 2 µA/K (-20 … 70 °C (-4 … 158 °F)); < 4 µA/K (-40 … -20 °C (-40 … -4 °F)) | |
Frequency range | field side into the control side: bandwidth with 0.5 Vpp signal 0 … 3 kHz (-3 dB) control side into the field side: bandwidth with 0.5 Vpp signal 0 … 3 kHz (-3 dB) |
|
Rise time | 10 to 90 % ≤ 10 ms | |
Galvanic isolation | ||
Input/Output | basic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff | |
Input/power supply | basic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff | |
Output/power supply | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff | |
Input/input | functional insulation, rated insulation voltage 50 V AC | |
Indicators/settings | ||
Display elements | LEDs | |
Labeling | space for adhesive label at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Electromagnetic compatibility | NE 21:2017 EN 61326-3-2:2018 |
|
Degree of protection | IEC 60529 | |
Protection against electrical shock | UL 61010-1:2012 | |
Ambient conditions | ||
Ambient temperature | -40 … 70 °C (-40 … 158 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 135 g | |
Dimensions | 20 x 124 x 115 mm (0.8 x 4.9 x 4.5 inch) , housing type B2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-type examination certificate | BAS 00 ATEX 7240 X | |
Marking | II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I |
|
Output | Ex ia, Ex iaD | |
Voltage | 25.2 V | |
Current | 93 mA | |
Power | 585.3 mW | |
Internal capacitance | 1.05 nF | |
Internal inductance | 0 | |
Supply | ||
Maximum safe voltage | 250 V rms (Attention! The rated voltage can be lower.) | |
Input | ||
Maximum safe voltage | 250 V rms (Attention! The rated voltage can be lower.) | |
Certificate | TÜV 99 ATEX 1499 X | |
Marking | II 3G Ex nA II T4 | |
Galvanic isolation | ||
Input/Output | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V | |
Output/power supply | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2018 , EN 60079-11:2012 , EN 60079-15:2005 | |
International approvals | ||
UL approval | E106378 | |
Control drawing | 116-0345 (cULus) | |
IECEx approval | ||
IECEx certificate | IECEx BAS 04.0014X | |
IECEx marking | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc |
KFD2-SCD2-EX2.LK
Ex-erotin analogialähtöviesteille
- 2-kanavainen galvaaninen erotin
- 24 VDC jännitesyöttö (Power Rail)
- Virtalähtö maksimi 650 Ω kuormalle
- HART I/P ja venttiilin asennoitin
- Johdinkatkoksen valvonta
- Kotelon leveys 20 mm
- SIL 2